ANTRACK V1
ANTRACK V1
| Function | BTC/BCH/BSV SHA256 Hydro-cooling Miner |
| Specifications | 24kW 4 Hydro-cooling Miner Rack |
Specification Details For ANTRACK
| Product Glance | |
| Model | ANTRACK |
| Version | V1 |
| Capacity | 4 units ANTMINER (S21 Hyd.) |
| Maximum load,kW | 24 |
| Detailed Characteristics | |
| Hardware configuration | |
| Size (width*height*depth),mm | 600*2000*1000 |
| Net weight, kg | 300 |
| Network connection mode | EJ45 Ethernet 10/100M |
| Power supply | |
| Power supply AC input voltage, Volt(1-1) | 380~415 |
| Power supply AC input frequency range, Hz | 50~60 |
| Power supply AC Input current, Amp(1-2) | 80 |
| Environment requirements | |
| Ambient temperature, °C | 15~45 |
| Water flow, L/min | 32.0~40.0 |
| Water pressure, bar | ≤3.5 |
| Working fluid(1-3) | Deionized water/Pure water |
| Liquid PH | 8.5~9.5 |
| Storage temperature, °C | -20~70 |
| Operation humidity(non-condensing), RH | 10~90% |
NOTE:
(1-1) Caution: Wrong input voltage may probably cause miner damaged
(1-2) Three-phase AC input.
(1-3) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.